Factory Use Security Alarm System with Conventional Fire Alarm Control Panel

Still deciding? Get samples of $ !
Order Sample

Product Description

Basic Specifications
Model NO.PZ1002
UsageFire, Smoke
CertificationCE
Alarm Volume≥100dB (within 1m)
Networking ModeAlarm
Receive Frequency485/232
Wiring ModeSub-Line System
Number of Zones2
Primary AC90-270VDC
Standby Battery2*12V
Detector Voltage24VDC
Max Detectors/Zone30
Weight3kg (Without Battery)
Package Size30.00cm * 28.00cm * 25.00cm
Gross Weight3.000kg
Specification108*143*40mm
Production Capacity500,000/Month
HS Code8531100000
Installation Instructions
Conventional Fire Alarm Control Panel Installation
SAFETY FIRST

THIS EQUIPMENT MUST ONLY BE INSTALLED AND MAINTAINED BY A SUITABLY SKILLED AND TECHNICALLY COMPETENT PERSON. THIS EQUIPMENT IS A PIECE OF CLASS 1 EQUIPMENT AND MUST BE EARTHED. DO NOT CHANGE ANY CONNECTIONS WITH POWER APPLIED.

Installation Procedure: All cables must be installed in accordance with applicable national and regional standards. Fire resistant, screened cable should be used throughout. Mains wiring should be segregated from extra low voltage field wiring. For permanently connected equipment, a readily accessible disconnect device shall be incorporated external to the equipment.

Testing the Panel: When testing with the lid open, always isolate the Mains and disconnect batteries. Position and connect two 12V batteries as required. The Battery/Power Supply Fault indicator will light and the beeper will sound until Mains power is applied.

Technical Parameters
Input VoltageAC 100-240V, 50/60Hz
Internal PowerDC 30V 3A
Total Output Current≤200mA @ 220V
Chipset32-bit Micro processor
Operating Temp0ºC ~ +50ºC
Zone Capacity1-8 Zone(s)
Backup BatteryDC 12V/2.2AH * 2
Dimension325x265x100mm
MaterialIron
EMI ImmunityHigh Immunity
External Indicators
  • Reset / Resound / Test Zone Lamps
  • Evacuate
  • Silence Alarm Sounders
  • Silence Fault Sounders
Internal Indicators
  • Open circuit zone fault
  • Short circuit zone fault
  • Zone isolate
  • Engineer test selected
Product Display
Frequently Asked Questions
Q1: How many smoke detectors can be connected to each zone?
Depending on the specific zone requirements, typically each zone can support 20-30 smoke detectors.
Q2: Does the control panel include backup batteries?
The standard package does not include the two DC 12V/2.2AH batteries; they must be sourced separately.
Q3: What should I do if the panel shows an "Open Circuit Fault"?
Check if the wiring is broken or if the End-Of-Line device (EOLD) is disconnected. You may also need to adjust the potentiometer (VR1) to calibrate the zone voltage.
Q4: Is it safe to change connections while the power is on?
No, you must never change any panel connections while the power (Mains or Battery) is applied to avoid damage to the electronic components.
Q5: What are the primary output capabilities of the sounder circuits?
The panel features two sounder circuits. Additionally, ancillary connections allow for expansion modules like repeater panels or multiple sounder outputs.
Q6: What material is the control panel casing made of?
The enclosure is made of high-quality iron for durability and high EMI immunity.

Related Products